RFL SMX3/40 Page 7 of 24 Issue 2.02
User Manual
07 May 2009
Optional X21 Port Pin-out (when in DCE configuration) – D15M
Circuit Pin A Pin B Direction Notes
T Transmit Data 2 9 Input
R Receive Data 4 11 Output
C Control 3 10 Input Signal ignored
I Indication 5 12 Output Permanently on
S Signal Element
Timing
6 13 Output Timing signal transmitted
to network
G Ground 8 15
Screen / Drain
Must be earthed to shell
In either configuration, use 6 pair plus ground stranded cable with overall shield
(eg RS 111-8994).
Maximum recommended length in substations - 5m
Absolute maximum length - 10m.
The DCE configuration is used when the X21 link requires to be synchronised to the
network master clock signal that has been received from a co-located SMX3/40, or to
itself as master where network timing is unavailable. The timing signal is output on
pins 6 and 13.
DIP switches provide configuration options, see section 10.